Notes:
1. 310.15(B)(2)(3)(a)Exception No, 5 Circuit is Type AC cable or to Type MC cable without an
overall outer jacket under the following conditions:(1) Each cable has not more
than three current-carrying conductors. (2) The conductors are 12 AWG copper.(3)
Not more than 20 current-carrying conductors are bundled, stacked, or supported
on “bridle rings. (Load must be 18.6 amperes or less - ambient multiplier
1.04 x .6 x 30)) 2. 240.4(B)
Devices Rated 800 Amperes or Less.
The next higher standard overcurrent device rating (above the ampacity of the
conductors being protected) shall be permitted to be used, provided all of the
following conditions are met: (1) The conductors being protected are not part of
a multioutlet branch circuit supplying receptacles for cord and- plug-connected
portable loads. Also see Table 210.24 and Section 210.23.
3. Neutral Conductor.
(a) A neutral conductor that
carries only the unbalanced current from other conductors of the same circuit
shall not be required to be counted as a current carrying conductor.
(b) In a 3-wire circuit consisting of two phase wires and the neutral of a
4-wire, 3-phase, wye-connected system, a common conductor carries approximately
the same current as the line-to-neutral load currents of the other conductors
and shall be counted as a current carrying conductor.
(c) On a 4-wire, 3-phase wye circuit where the major portion (over 50 per cent)
of the load consists of nonlinear loads such as electric discharge lighting and
computer loads, harmonic currents are present in the neutral conductor and the
neutral shall be considered a current carrying conductor.
(d) Each current-carrying conductor of a paralleled set of conductors shall be
counted as a current carrying conductor.
4. Termination provisions
of equipment for circuits rated 100 amperes or less, or marked for 14 AWG
through 1 AWG conductors, shall be used only for one of the following:
(1) Conductors rated 60°C (140°F).
(2) Conductors with higher temperature ratings, provided the ampacity of such
conductors is determined based on the 60°C (140°F) ampacity of the conductor
size used.
(3) Conductors with higher temperature ratings if the equipment is listed and
identified for use with such conductors.
(4) For motors marked with design letters B, C, or D, conductors having an
insulation rating of 75°C (167°F) or higher shall be permitted to be used,
provided the ampacity of such conductors does not exceed the 75°C (167°F)
ampacity.
Termination provisions of equipment for circuits rated over 100
amperes, or marked for conductors larger than 1 AWG, shall be used only for one
of the following:
(1) Conductors rated 75°C (167°F)
(2) Conductors with higher temperature ratings, provided the ampacity of such
conductors does not exceed the 75°C (167°F) ampacity of the conductor size used,
or up to their ampacity if the equipment is listed and identified for use with
such conductors.
Author's Note: In general most terminals are rated for 75
degrees C. Conductors with 90 degree C insulations can be used on these
terminals provided they are not used at an ampacity higher than the 75 degree C.
ampacity. However, the 90 degree insulation ampacity can be used for
derating purposes. For example a No. 12 AWG copper 90 degree
C. THHN rated at 30 amperes can be used in a raceway with up to 9 current
carrying conductors on a 20 ampere circuit breaker since the derated
ampacity is 0.7 x 30 = 21 amperes.
75 degree terminations may be stamped as AL7CU.
Copyright Notice |