Grounding Electrode Conductor Size Selector
| |||
|
|
| ||
|
Notes: 1. Where multiple sets of service-entrance conductors are used the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 3. Where the grounding electrode conductor is connected to made electrodes that portion of the conductor that is the sole connection to the grounding electrode shall not be required to be larger than No. 6 copper wire or No. 4 aluminum wire. 4. Where the grounding electrode conductor is connected to a concrete-encased electrode that portion of the conductor that is the sole connection to the grounding electrode shall not be required to be larger than No. 4 copper wire. 5. Where the grounding electrode conductor is connected to a ground ring not smaller than No. 2. that portion of the conductor that is the sole connection to the grounding electrode shall not be required to be larger than the conductor used for the ground ring. | |||